Fire Hydrants
Provision & Siting
Testing Private Fire Hydrants
Fire Hydrants

Fire Hydrants

The design and installation of hydrant systems should be closely correlated with all other services being provided in the building, and ducts may be shared.

Underground Fire Hydrant

The design and installation of hydrant systems should be closely correlated with all other services being provided in the building, and ducts may be shared. The water supply to hydrants should be kept entirely independent from other water supplies including those for other fire-fighting systems.

Hydrant systems should be afforded all possible protection against frost.

Discuss your requirements or find out more about gas detection

Provision & Siting

When they are considered to be necessary, private fire hydrants should be provided within the confines of the site after consultation with the local water and fire authorities.

Fire Hydrants

When they are considered to be necessary, private fire hydrants should be provided within the confines of the site after consultation with the local water and fire authorities. Their installation should conform generally to this British Standard and also to any specific requirements of these authorities or the insurance company.

Fire hydrants should be positioned in such a way that the parking, loading and unloading of vehicles is unlikely to obstruct them, and in choosing locations for them regard should be paid to the availability of statutory hydrants in public thoroughfares nearby.

Where fire hydrants are to be installed, they should be included as part of a ring fire main system and be positioned not more than 90 m from an entry to any building on the site and not more than 90 m apart.

They should preferably be sited immediately adjacent to roadways or hard-standing facilities suitable for fire and rescue service appliances. To ensure that they remain usable during a fire they should be sited with consideration of the effect that falling debris and other possible occurrences during a fire might have on the continuing viability of the location, and should be not less than 6 m from the building or other risk.

Siting of underground fire hydrants in roadways should be avoided but where necessary the frame and over should be in accordance with BS 750 and capable of bearing the heaviest vehicle anticipated to use the roadway.

Underground fire hydrants should be in accordance with BS 750 and BS EN 14339. Pillar hydrants should be in accordance with BS EN 14384. Where pillar hydrants are installed, care should be taken to protect them from mechanical damage and from damage by frost.

Ring Main Supply

Where a number of fire hydrants or wet fire mains are required because of the area of the premises to be covered, the mains supplying these systems should be in the form of a ring main to form a complete circuit of the site. It is advisable for water to be supplied to the ring at more than one position, preferably from supplies obtained from different sources.

Isolating valves should be incorporated in the system so that sections of the ring main can be isolated to enable repairs to be carried out. Branches to town’s mains should also have an isolating valve and a non-return valve to suit the water undertaker’s requirement.

Discuss your requirements or find out more about gas detection

Fire Hydrants

Testing Private Fire Hydrants

Inspection of and, where practicable, a wet test of private underground fire hydrants should be made in conjunction with the fire authority and the owner or occupier of the premises or their representative.

Inspection of and, where practicable, a wet test of private underground fire hydrants should be made in conjunction with the fire authority and the owner or occupier of the premises or their representative. Where such hydrants are supplied from mains, arrangements should also be made with the water undertaking before tests are carried out.

During these inspections and tests the condition of the following should be checked and noted for remedial action if necessary:

  • Pits
  • Frames
  • Covers
  • Surface paving round edges of frames
  • Depth of outlet below the frame, which should be no more than 300 mm below ground level
  • Method of indication by means of hydrant indicator plate or sticker

The test should include flushing out the outlet and checking the outlet connection. The flow and pressure at the outlet should also be measured and noted.

On completion of the test, the operation of the frost valve (where fitted) should be checked, and the pit should be left empty and clean.

Trusted by leading organisations

We work with many leading businesses and organisations

five-stars
I could not recommend them enough

I am really pleased with the service provided by Artius Fire Protection. As a leaseholder with Westminster Council, I took the initiative to upgrade my front door, which was over 25 years old, to an approved FD30 rated fire door. After extensive research, I encountered several companies, but many were only interested if I was part of a larger bulk order. Artius Fire Protection, on the other hand, was more than happy to assist with a one-door installation tailored to my needs. They were very responsive and provided full support during the process of replacing my door with the council, which was not exactly straightforward. They even arranged for door colour samples to be sent to my address to help me decide on the best colour. During the initial consultation to help me choose the right door for me, my emails were always answered almost immediately. Based on my experience, I could not recommend them enough.

Nigel , Westminster Council Leaseholder
five-stars
An Outstanding Experience

Working with Artius has been an outstanding experience. Their professionalism and deep expertise in the fire protection field is truly unmatched. Not only are they highly knowledgeable, but they’re also incredibly friendly and easy to work with. I have complete confidence in their ability to deliver top-tier service every time.

Richard Scott, Bellrock Account Manager
five-stars
Our Preferred Supplier

Artius fire protection have been our preferred supplier for over 10 years. I cannot fault their level of service and professionalism. I would highly recommend their services to all.

Rose Dosanjh, Purchasing Dept, Toni & Guy
five-stars
Insightful advice, great service!

Keenan is a great guy to work with, his knowledge and expertise is second to none. Great service supplied by the wider team, the recommendation I was given to hire this company for my sprinkler system was spot on.

Claude Devlin, Trustpilot Review
five-stars
Artius Provide Grade 1 Service
The Royal College of Physicians have used the services of Artius for several years now. Being a Grade 1 listed building, we need to ensure that we have reliable suppliers working on site who deliver grade 1 service. Artius provide exactly that for us.
Nigel Crowdy, Workplace Manager, Soft Services /College Bedell